Transformers are critical components in electrical power systems, responsible for stepping up or stepping down voltage levels to facilitate efficient transmission and distribution of electricity.
Several important specifications define the performance and characteristics of transformers:
Voltage Rating: This specification indicates the maximum voltage that the transformer can handle safely. It includes both the primary (input) and secondary (output) voltage ratings.
Power Rating (kVA): The power rating of a transformer, measured in kilovolt-amperes (kVA), signifies its capacity to handle electrical power. It determines the maximum load that the transformer can carry without overheating.
Frequency: Transformers are designed to operate at specific frequencies, typically either 50 Hz or 60 Hz, depending on the power system requirements of the region.
Insulation Class: Transformers are insulated to withstand high voltages and protect against electrical breakdown. The insulation class specifies the maximum temperature that the transformer winding can reach under normal operating conditions.
Impedance: Transformer impedance represents the resistance to the flow of current in the transformer windings. It affects the voltage regulation and fault current capability of the transformer.
The impedance range of a transformer can vary depending on factors such as the design, construction, and intended application of the transformer. However, transformers generally have impedance values ranging from around 2% to 10%.
Efficiency: Transformer efficiency indicates how effectively the transformer converts electrical power from the primary side to the secondary side. Higher efficiency transformers minimize energy losses and improve overall system performance.
The peak efficiency of a transformer occurs when the amount of power lost as heat in the copper winding (copper loss) equals the power lost due to magnetic flux in the transformer core (iron loss). For transformers designed to handle varying loads, optimal efficiency is achieved when the load is around 75% of the transformer's full capacity. These transformers, commonly known as distribution transformers, are specifically engineered to perform efficiently under typical operating conditions, where the load fluctuates throughout the day.
Temperature Rise: Transformers experience temperature rise during operation due to electrical losses and load currents. The temperature rise specification defines the maximum allowable temperature increase above the ambient temperature under full-load conditions.
Cooling Method: Transformers can be cooled using various methods such as air, oil, or water. The cooling method affects the transformer's thermal performance and determines its suitability for specific applications and environments.
Winding Configuration: Transformers may have different winding configurations, including single-phase or three-phase, as well as various connection arrangements such as delta or wye.
Size and Weight: The physical dimensions and weight of a transformer are important considerations for installation, transportation, and space requirements in substations or electrical facilities.
Overload Capacity: Transformers should be capable of withstanding temporary overload conditions without damage. The overload capacity specification indicates the extent to which the transformer can handle overload conditions safely.
Noise Level: Transformers may produce audible noise during operation, particularly in distribution transformers. Noise level specifications define the maximum permissible sound level emitted by the transformer.
Losses in transformers
Copper Losses (I²R Losses):
- Resistance Losses: When electrical current flows through the winding conductors of a transformer, resistance in the wires causes energy to be lost as heat according to the formula I²R, where I is the current and R is the resistance of the winding.
- These losses occur in both the primary and secondary windings and are proportional to the square of the current passing through the winding.
Iron or Core Losses:
- Hysteresis Losses: These losses occur due to the repeated magnetization and demagnetization of the transformer core as the alternating current passes through it. This results in energy dissipation in the form of heat.
- Eddy Current Losses: When alternating current flows through the transformer core, it induces circulating currents called eddy currents in the core material. These currents encounter resistance in the core material, leading to additional energy losses in the form of heat.
Total Losses:
- The total losses in a transformer are the sum of the copper losses and iron losses. These losses are typically expressed in watts or kilowatts and represent the amount of power wasted during the operation of the transformer.
Tap changers
work by physically changing the connection point of the transformer winding. This adjustment allows for increasing or decreasing the number of turns in the winding and hence altering the voltage ratio between the primary and secondary sides of the transformer.
Types of Tap Changers:
On-Load Tap Changer (OLTC): On-load tap changers are designed to change tap positions while the transformer is energized or under load. This allows for voltage adjustment without interrupting power supply, making them suitable for applications where continuous operation is essential.
Off-Circuit Tap Changer (OCTC): Off-circuit tap changers, also known as de-energized tap changers, require the transformer to be de-energized during tap changes. While this method is less convenient as it involves a temporary interruption of power, it is often used in smaller transformers or applications where load interruptions are permissible.
Vector group
DY11 Vector Group:
- The DY11 vector group signifies the following winding configuration:
- Primary Winding (High Voltage, HV):
- Connected in delta (Δ) configuration.
- The polarity of phase winding A is connected to the non-polarity end of phase winding B (DAB connection).
- Line currents lead the phase currents by 30°.
- Secondary Winding (Low Voltage, LV):
- Connected in wye (Y) configuration.
- The LV winding lags the HV winding by 30°.
- Primary Winding (High Voltage, HV):
- In summary, DY11 indicates that the LV leads the HV by 30°. Therefore, the HV winding should be DAC connected.
- The DY11 vector group signifies the following winding configuration:
Other Vector Groups:
- Here are some additional vector groups commonly encountered:
- Dyn1 (Yd1): The LV winding leads the HV by 30 degrees.
- Ynd1 (Yyn0): The LV winding lags the HV by 30 degrees.
- Ynd11 (Yyn5): Similar to Ynd1 but with a neutral point brought out.
- Dyn11 (Yd5): The LV winding leads the HV by 30 degrees, and the neutral point is brought out.
- Yzn11 (Yz5): The LV winding lags the HV by 30 degrees, and the neutral point is brought out.
- Here are some additional vector groups commonly encountered:
Applications:
- These vector groups have specific applications:
- Dyn1: Used in distribution systems when generator transformers are YNd11.
- Dyn11: Suitable for distributing balanced voltage, maintaining the same phase shift as the generating voltage, and eliminating zero-sequence current.
- Yzn11: Useful for systems with different types of harmonics and nonlinear loads (e.g., furnace heaters, VFDs), where the 30-degree voltage shift nullifies the 3rd harmonics in the supply system.
- These vector groups have specific applications:
Specific standards followed.
Indian Standards (IS):
The Bureau of Indian Standards (BIS) provides guidelines for transformer design and performance in India. While IS 2026 primarily focuses on power transformers, IS 1180 covers distribution transformers.
As per IS 2026, Clause 7.3.1, the rated kVA of a transformer should not be less than the apparent power (kVA) of the load it is intended to supply. However, there may be exceptions or specific requirements based on the application and the standards followed by the utility or regulatory authority.
British Standards (BS):
In the United Kingdom, transformer standards are outlined by the British Standards Institution (BSI). BS EN 60076 series provides specifications for power transformers, including requirements for performance, testing, and safety.